Lighting measurement

We measure illuminance and uniformity with a calibrated lux meter, compare the results with the standard and recommend the next steps. For official reports in Slovakia we work with an authorised partner.

Intersnack – osvetlenie skladovej haly, expedície a exteriéru
500 lx

maintained illuminance for computer work according to EN 12464-1

0.60

minimum uniformity of illuminance for computer work

200 – 350 lx

is often measured on office desks instead of the required 500 lx

1 lx

minimum on an escape route during a power failure according to EN 1838

When measurement pays off

A lux meter shows how much light actually falls on the workplace – not how much the catalogue promises. We measure indoors and outdoors and always compare the result with the standard for the activity in question.

Before a refurbishment

Measuring the current situation shows where light is lacking and where there is more than necessary. It is the basis for a lighting design.

After a lighting replacement

Repeating the measurement after installation verifies whether the new lighting meets both the design and the standard. You have the before and after in black and white.

Complaints about the light

Eye strain, dark spots, shadows between racks? Measurement shows where light is missing and where the lighting is uneven.

Occupancy approval and change of use

For occupancy approval, a change of use or when a workplace is put into operation, the authorities may require a measurement report. In Slovakia we provide it through an authorised partner.

Emergency lighting

During a power failure, emergency lighting must provide at least 1 lx on the escape route. In Slovakia we arrange measurement with a report through a partner.

Outdoor areas

Sites, car parks and loading ramps are measured after dark. Public lighting is assessed as part of the inventory and audit.

What we measure and what we compare it with

With a lux meter we measure illuminance in a grid of points on the working plane or on the floor. From the measured values we determine the average and minimum illuminance and the uniformity and compare them with the requirements of the standard for the activity in question.

UGR glare cannot be measured with a lux meter – it is verified by calculation during the DIALux lighting design.

STANDARDWHAT IS ASSESSED
EN 12464-1illuminance and uniformity of indoor workplaces
EN 12464-2outdoor workplaces – sites, loading ramps, car parks
EN 12193sports facilities – pitches and halls
EN 1838emergency lighting of escape routes (through a partner in Slovakia)

Check measurement and official reports

Carried out in-house

Check measurement with a calibrated lux meter

  • the situation before a refurbishment
  • a check after a lighting replacement
  • comparison with the standard for the activity
  • recommendations for improvement

Useful when deciding on a modernisation and for checking a delivery. It can also be part of a turnkey delivery – for the production hall in Partizánske (318 luminaires, 300 lx required throughout the hall) the scope of work included a post-installation illuminance measurement. More in the case study (in Slovak).

Through an authorised partner

Measurement with a report for the authorities

In Slovakia, under Decree No. 541/2007 Coll. of the Slovak Ministry of Health, the photometric quantities of artificial workplace lighting are determined by measurement and the results are recorded in a lighting measurement report. We provide such a report – for example for occupancy approval or for the regional public health authority (RÚVZ) – through an authorised partner.

In the same way we arrange measurement of emergency lighting and daylight.

How the measurement works

01

Brief

We agree which areas to measure, what they are used for and which standard to compare them with.

02

On-site measurement

We measure in a grid of points with a calibrated lux meter – so that daylight does not distort the result.

03

Evaluation

Average and minimum illuminance and uniformity compared with the standard.

04

Recommendations

If the lighting does not comply, we propose a solution – from adjusting the layout to a new design.

05

Check after replacement

After the installation we repeat the measurement and compare the situation before and after the replacement.

What measurement most often reveals

Too little light on desks

In offices, only 200 – 350 lx is often measured on desks instead of the required 500 lx. More in the article Office lighting standards (in Slovak).

Dark spots and shadows

Dark corners and shadows from racks or furniture pull the uniformity below the value the standard requires for the activity.

Ageing luminaires

Discharge and fluorescent lamps give less light with age for the same consumption. In Gbely, the efficiency of the original luminaires had dropped to 60 % due to age, and measurements at the switchboards revealed 30 faulty luminaires out of 499.

Frequently asked questions

Answers to the questions customers ask us most often about lighting measurement.

What values must the lighting meet?

They are set by the standard according to the activity. For computer work in an office, EN 12464-1 requires a maintained illuminance of 500 lx and a uniformity of at least 0.60. Different values apply to warehouses, production areas or corridors – you will find them on our solutions by space pages.

Why do we measure more after the replacement than the standard requires?

The standard prescribes maintained illuminance – a value the lighting must not fall below even after years of operation. New luminaires are therefore designed with a margin for ageing and soiling, which the calculation takes into account through the maintenance factor.

Can glare be measured?

Not with a lux meter. Indoors, glare is assessed with the UGR index, which is determined by calculation – that is why we verify it during the DIALux lighting design.

We need a report for occupancy approval. Can you provide it?

In Slovakia, yes. We provide measurement with a report for the authorities, for example for occupancy approval or for the RÚVZ, through an authorised partner. We carry out routine check measurements ourselves with a calibrated lux meter.

Do you also measure emergency lighting?

In Slovakia we arrange emergency lighting measurement through a partner. During a power failure, EN 1838 requires at least 1 lx on the escape route and at least 0.5 lx in open areas.

When is lighting measured?

We measure artificial lighting so that daylight does not distort the result – indoors often after dark, outdoors always. We agree the time of measurement around your operations.

What if the measurement shows that the lighting does not comply?

We propose a solution. Sometimes it is enough to adjust the layout or replace some of the luminaires; at other times a new lighting design with a calculation of savings and payback is worthwhile.

Do you also assess public lighting?

Yes, as part of the public lighting inventory and audit: we map the light points and switchboards, measure the consumption and assess the lighting of each section by calculation according to EN 13201.

Read on our blog

All articles →

Related services